Common faults of IC card meters
Classification:Company News Release time:2023-06-14 15:49:23

icCommon faults of card meter

The device does not display

The digital tube displays nothing, or the user information to be queried

1reason   

11The fuse is blown.   

11The power transformer on the control board is faulty.   

113 ICThe jam is too dirty or inserted in reverse.WillICWipe the card clean before inserting the card.If the problem has not been solved by the above method, the back cover of the integrated circuit controller needs to be opened, inserted into the management card, press the clear button to clear it, and re-correct it.ICEnter relevant information on the card.

The device shows electrical energy.But the output is powered

21reason   

211The deviceDZone48The coil burned.   

212The terminal strip wiring is loose.   

22Troubleshooting   

221Check the deviceDZ—48Whether the coil is burned or not, it will be repaired or replaced.   

222Use a screwdriver to tighten the terminal screws to make them well-wired.

The device shows that the electrical energy is zero.But don't jump

31reason   

311The deviceDZone48The coil burns or the neutral wire is broken, causing it to not trip when it should be tripped.   

312The terminal strip leads are loose.   

32Troubleshooting   

321Check the deviceDZ—48Whether the coil is burned or whether the neutral wire is broken, if the neutral wire is burned or the neutral wire is broken, replace or connect it.   

322Tighten the terminal screws to ensure good wiring.

The number of power attacks does not match the number displayed by the computer

41reason   

411Electricity meter andICThe constants of the card are inconsistent.   

412The sensor head and dial position of the photosensitive sensor are inappropriate.   

413The aluminum disk of the power meter is dirty, causing misreading sensors.   

42Troubleshooting   

421FixedICcard constant so that it is consistent with the power meter constant.

422Open the meter cover and adjust the position of the photosensitive sensor's sensor head and dial to keep the rotation number of the electricity meter consistent with the photosensitive pulse.

423Wipe or clean the dial dust points so that the sensor can conduct normal readings.


>