The power meter is a multifunctional intelligent power meter with programmable measurement, display, RS485 digital communication and electric energy pulse output. It can complete three-phase electric parameter measurement (three-phase voltage, three-phase current, active power, reactive power, apparent power, power factor, frequency, etc.), harmonic measurement, power grid quality analysis (voltage crest factor, current K factor, telephone waveform factor, voltage and current unbalance, voltage and current sequence quantity, etc.), four-quadrant electric energy metering, multi-rate electric energy metering, maximum demand recording, SOE event recording, data display, collection and transmission. It can be widely used in substation automation, distribution automation, intelligent buildings, and internal enterprise electric energy measurement, management, and assessment. The measurement accuracy is 0.5 level, and it realizes LCD field display and remote RS-485 digital interface communication, using standard MODBUS-RTU communication protocol.
The network multifunctional power meter has a variety of extended functions for selection: 4-way analog quantity transmission output, 4-way relay output (can be used as local electric parameter alarm or remote control output), and 4-way switch quantity input.
parameter |
performance |
||
Input Measurement |
wiring |
Three-phase four-wire/three-phase three-wire |
|
Voltage |
Range |
AC400V/100V |
|
Overload |
Continuous: 1.2 times, instantaneous: 2 times/1S |
||
Power consumption |
<0.3VA |
||
impedance |
>1.8MΩ |
||
Accuracy |
RSM measurement, accuracy level 0.2, 0.5, 1.0 |
||
Current |
Range |
AC5A/1A |
|
Overload |
Continuous: 1.2 times, instantaneous: 10 times/5S |
||
Power consumption |
<0.4VA |
||
impedance |
<15mΩ |
||
Accuracy |
RSM measurement, accuracy level 0.2, 0.5, 1.0 |
||
frequency |
45-65HZ, accuracy ±0.02HZ |
||
power |
Active power level 0.5, level 1.0 Reactive power level 2.0, power factor level 0.5 |
||
Electricity |
This month, last month, and the month before that with multiple tariffs (optional); active energy level 0.5, level 1.0; reactive energy level 2.0 |
||
Harmonics (optional) |
Voltage and current 2~31 harmonics, accuracy 1% |
||
SOE Event Log |
Save the latest 64 SOE event records |
||
Demand |
Record the maximum active power, reactive power, apparent power demand and occurrence time |
||
Output Module |
Power pulse output |
Passive optocoupler open collector output, pulse constant 3600 |
|
communication |
RS485 communication interface, MODBUS-RTU protocol, communication baud rate 1200~9600 |
||
Switch output (optional) |
4 relay outputs, contact capacity AC250V/3A, DC30V/3A |
||
Switch input (optional) |
4-way passive dry node input |
||
Transmitter output (optional) |
4-way (DC0~20mA, DC4~20mA, DC0~5V, etc.) transmission output, accuracy 0.5 level |
||
Auxiliary power supply |
AC/DC85-265V, AC220V (default), AC380V±5%, <5VA |
||
show |
FSTN LCD display |
||
environment |
Working temperature: -10-55℃, storage temperature: -20-85℃ |
||
Safety |
Insulation: Signal, power, output terminal to shell resistance > 5MΩ Withstand voltage: Signal input, power, output > 2KV |
Appearance code |
Overall dimensions (mm) |
Opening size (mm) |
Minimum installation distance |
Depth(mm) |
|
Level(mm) |
Vertical(mm) |
||||
120 |
120×120 |
111×111 |
120 |
120 |
80 |
96 |
96×96 |
91×91 |
96 |
96 |
80 |
80 |
80×80 |
76×76 |
80 |
80 |
80 |
72 |
72×72 |
67×67 |
72 |
72 |
80 |