The segmented automatic protection is suitable for primary systems that need to realize the automatic protection function of two incoming power sources. Only two line automatic protection switches are needed to realize the automatic protection of busbar equipment, reverse busbar automatic protection, line automatic protection, and reverse line automatic protection. At the same time, it can meet the relevant protection functions of overhead lines and cable lines with voltage levels of 35KV and below. It can be installed in small ring network cabinets such as solid cabinets and inflatable cabinets. The perfect design ensures that the device can operate reliably for a long time in harsh environments.
Technical indicators
◆ AC rated current: 5A or 1A (please specify when ordering);
◆ AC rated voltage: 57.7V or 100V (please specify when ordering);
◆ Working frequency: 50HZ;
◆ Working power supply: AC/DC85-265V;
◆ Power supply: internal 24V;
◆ Current measurement accuracy: 0.5 level;
◆ Voltage measurement accuracy: 0.5 level;
◆ Protection action exit time: 1.5 times the fixed value protection action time is not more than 35ms;
◆ Switch-on node: Continuously connect AC/DC220V, 5A current (pure resistive load).
Measurement and control function
◆ Remote measurement: voltage, current, active power, reactive power, power factor, etc., can be set to display primary value or secondary value;
◆ Remote signal quantity: The device has 8 remote signal input quantities;
◆ Event record: The device can record 64 events including input position change, device self-check, protection action, etc., which will not be lost in case of power failure;
◆ Remote control: The device can remotely open and close the switch and remotely call and modify the protection setting through the remote background.
Protection function
◆ Unlimited overcurrent protection
◆ Two-stage time-limited overcurrent protection
◆ Overload protection
◆ Inverse time overload protection
◆ Zero sequence overcurrent protection
◆ Zero sequence overvoltage protection
◆ PT disconnection monitoring
◆ Overvoltage protection
◆ Pressure loss protection
◆ Mother-to-mother backup power supply
◆ Incoming line standby automatic switching
◆ Reverse standby automatic switching
Communication Function
◆ You can choose a magnetically isolated high-speed standard RS485 interface or a magnetically isolated high-speed standard CAN2.0B interface (choose one of the two, please specify when ordering);
◆ RS485 interface communication protocol is IEC 60870-103 communication protocol;
◆ The communication protocol of CAN2.0B interface is IEC 60870-104 protocol.